Bodine 196352 B50-CAN - Emergency Ballast - 90 Min. - Operates (1) or (2) T5, T8, T9, T10, T12 Fluoresent Lamps - Dual Voltage 120/347V
![]() Click to enlarge |
|
The B50-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts.
When AC power fails, the B50-CAN immediately switches to the emergency mode, operating either one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the B50-CAN automatically returns to the charging mode
APPLICATION
The B50-CAN fluorescent emergency ballast works in conjunction with an AC ballast to convert new or existing fluorescent fixtures into emergency lighting. The emergency ballast consists of a high-temperature nickel-cadmium battery, charger and electronic circuitry in one compact red case. The B50-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The B50-CAN is suitable for indoor locations. It is not suitable for air handling heated air outlets or wet, damp or hazardous locations. For information about specific lamp and ballast compatibility, please call the factory.
OPERATION
When AC power fails, the B50-CAN immediately switches to the emergency mode, operating either one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the B50-CAN automatically returns to the charging mode.
INSTALLATION
The B50-CAN does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The B50-CAN may be installed inside, on top of or remote from the fixture. The emergency ballast may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C.
cUL, CSA and CODE COMPLIANCE
The B50-CAN has been tested per applicable standards and is cUL Listed and CSA Certified for factory or field installation. Emergency illumination time exceeds the National Electrical Code (NEC), Life Safety Code (NFPA-LSC), National Building Code of Canada (NBC), National Fire Code of Canada (NFC) and UL/CSA 90-minute requirements.
-
-
Stock Code
Bodine_B50-CAN
Brand
Philips
Family
CSA Certified Emergency Lighting Equipment
Part No
196352
Length (in)
13.3" (339mm)
Width (in)
2.4" (60mm)
Height (in)
1.5" (38mm)
Voltage (V)
120/347 VAC, 60 Hz
Input Current
280mA
Wattage (w)
4.0 Watts
Bulb Type
Fluorescent Lamps
Switch Type:
Test Switch: Single Pole
Lumens (Initial)
1400 Lumens
Battery Back Up
Yes
Battery Type:
High-Temperature, Maintenance-Free Nickel-Cadmium Battery 7- to 10-Year Life Expectancy
Recharge Time:
24 Hrs
Max. Charge Current
280mA
Operates
The B50-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving.
Start Temp. (Min)
0°C (32°F)
Start Temp. (Max)
55°C (131°F)