Bodine B50LP - Emergency Ballast - 90 Min. - Operates (1) or (2) T8, T9, T10, T12 Fluoresent Lamps - Dual Voltage 120/277V

Bodine B50LP - Emergency Ballast - 90 Min. - Operates (1) or (2) T8, T9, T10, T12 Fluoresent Lamps - Dual Voltage 120/277V
Click to enlarge
Price Per Item: $220.00
Availability: DISCONTINUED
Model: Bodine_B50LP
Manufacturer: Philips
Average Rating: Not Rated

Qty: Add to Wish List
(This product has a minimum quantity of 1000)

The B50LP can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving fluorescent lamps. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary

When AC power fails, the B50LP automatically switches to emergency power, operating one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the emergency ballast returns to the charging mode and, using a patented circuit, delays AC ballast operation for approximately three seconds to prevent false tripping of the AC ballast end-of-lamp-life shutdown circuits.

APPLICATION

The B50LP low-profile emergency ballast works in conjunction with a low-profile or standard-size AC ballast to convert new or existing fluorescent fixtures into unobtrusive emergency lighting. The emergency ballast consists of a high-temperature nickel-cadmium battery, charger and electronic circuitry in one compact case. The B50LP can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving fluorescent lamps. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The B50LP is suitable for indoor and damp locations and for sealed & gasketed fixtures, including fixtures rated for wet locations. It is not suitable for air handling heated air outlets or wet or hazardous locations. For information about specific lamp and ballast compatibility, please contact the factory. Recommended applications include: emergency lighting for pendant, cove, recessed indirect/direct, surface-mount and architectural lighting commonly used in office, hospitality, health care, retail and educational facilities.

OPERATION

When AC power fails, the B50LP automatically switches to emergency power, operating one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the emergency ballast returns to the charging mode and, using a patented circuit, delays AC ballast operation for approximately three seconds to prevent false tripping of the AC ballast end-of-lamp-life shutdown circuits.

INSTALLATION

The B50LP does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The B50LP may be installed inside, on top of or remote from the fixture. The emergency ballast may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C.

EMERGENCY ILLUMINATION

Depending on the number (one or two), wattage and type of lamps selected, the B50LP produces 750 to 1300 lumens initial emergency light output (see Table 2). If two-lamp operation is selected, light output is evenly divided between the lamps for better distribution of emergency illumination.

 

B50LP

Low-Profile Emergency Lighting Equipment


Specification grade;
High lumen, low profile
End-of-lamp-life compatible

 

Product Summary

 

  • UL Listed
    Factory or Field Installation
    (Indoor and Damp)
  • Illumination Time
    90 Minutes
  • Initial Light Output
    750 - 1300 Lumens
  • Full Warranty
    5 Years (NOT pro-rata)
  • Dual Input Voltage
    120/277 VAC, 60 Hz
  • AC Input Current
    200 mA
  • AC Input Power Rating
    4.0 Watts
  • Test Switch
    Single Pole
  • Battery
    High-Temperature, Maintenance-Free
    Nickel-Cadmium Battery
    7- to 10-Year Life Expectancy
  • Battery Charging Current
    180 mA
  • Recharge Time
    24 Hour
  • Charging Indicator Light
    LED
  • Temperature Rating (Ambient)
    0°C to +50°C (32°F to 122°F)
  • Dimensions
    21.5" x 1.18" x 1.18"
    (546 mm x 30 mm x 30 mm)
    Mounting Center 21.1" (536 mm)
  • Weight
    3.3 lbs. (1.5 kg)
  • Stock Code Bodine_B50LP
    Brand Philips
    Family Flourescent Emergency Ballast, Low-Profile for Space-Limited Fixtiures
    Part No B50LP
    Length (in) 21.5" (546mm)
    Width (in) 1.18" (30mm)
    Height (in) 1.18" (30mm)
    Voltage (V) 120/277VAC, 60Hz
    Input Current 200mA
    Wattage (w) 4.0 Watts
    Bulb Type Fluorescent Lamps
    Switch Type: Test Switch: Single Pole
    Lumens (Initial) 1300 Lumens
    Battery Back Up Yes
    Battery Type: High-Temperature, Maintenance-Free Nickel-Cadmium Battery 7- to 10-Year Life Expectancy
    Recharge Time: 24 Hrs
    Max. Charge Current 180mA
    Operates The B50LP can be used with most 17 - 215 W (2’ - 8’) T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving fluorescent lamps
    Start Temp. (Min) 0°C (32°F)
    Start Temp. (Max) 50°C (122°F)
    Weight (lb.) 3.3 lbs
    UL Listed UL and Code Compliance
    Case Quantity 1
    Warranty 5 Years (NOT pro-rata)
Write Review
Your Name:


Your Review: Note: HTML is not translated!

Rating: Bad            Good

Enter the code in the box below:

There are no additional images for this product.