Bodine B70A-CAN - Emergency Ballast - 90 Min. - Operates (1) x 17 - 32W T8 or (1) x 20 - 40W T10 or T12 Fluorescent Lamp - 120/347V

Bodine B70A-CAN - Emergency Ballast - 90 Min. - Operates (1) x 17 - 32W T8 or (1) x 20 - 40W T10 or T12 Fluorescent Lamp - 120/347V
Click to enlarge
Price Per Item: $150.00
Availability: DISCONTINUED
Model: Bodine_B70A-CAN
Manufacturer: Philips
Average Rating: Not Rated

Qty: Add to Wish List
(This product has a minimum quantity of 1000)

 

When AC power fails, the B70A-CAN immediately switches to the emergency mode, operating one lamp at a reduced lumen output for a minimum of 90 minutes. Two-hour duration may be selected with one 17 - 32 W T8 or with one 20 - 40 W T10 or T12 fluorescent lamp. When AC power is restored, the B70A-CAN automatically returns to the charging mode.

APPLICATION

The B70A-CAN fluorescent emergency ballast works in conjunction with the AC ballast to convert new or existing fluorescent fixtures into emergency lighting. The emergency ballast consists of a high-temperature nickel-cadmium battery, charger and electronic circuitry in one compact red case. The B70A-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving, and (4-pin) compacts. It is also compatible with most one-, two-, three- or four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The B70A-CAN is suitable for indoor locations. It is not suitable for air handling heated air outlets or wet, damp or hazardous locations. For information about specific lamp and ballast compatibility, please call the factory.

OPERATION

When AC power fails, the B70A-CAN immediately switches to the emergency mode, operating one lamp at a reduced lumen output for a minimum of 90 minutes. Two-hour duration may be selected with one 17 - 32 W T8 or with one 20 - 40 W T10 or T12 fluorescent lamp. When AC power is restored, the B70A-CAN automatically returns to the charging mode.

INSTALLATION

The B70A-CAN does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The B70A-CAN may be installed inside, on top of or remote from the fixture. The emergency ballast may be remotely installed up to half the distance the AC ballast manufacturer recommends remoting the AC ballast from the lamp or up to 50 feet, whichever is less. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C.

cUL, CSA and CODE COMPLIANCE

The B70A-CAN has been tested per applicable standards and is cUL Listed and CSA Certified for factory or field installation. Emergency illumination time exceeds the National Electrical Code (NEC), Life Safety Code (NFPA-LSC), National Building Code of Canada (NBC), National Fire Code of Canada (NFC) and UL/CSA 90-minute requirements.


B70A-CAN

CSA Certified Emergency Lighting Equipment


Two-hour emergency illumination

Product Summary

  • cUL LISTED/CSA CERTIFIED
    Factory or Field Installation
  • Illumination Time
    90 Minutes (Standard) or
    120 minutes
    (One 17-32 W T8, One 20-40 W T10 or T12)
  • Initial Light Output
    600 - 700 Lumens
  • Full Warranty
    3 Years (NOT pro-rata)
  • Voltage
    120/347 VAC, 60 Hz
  • AC Input Current
    280 mA
  • AC Input Power Rating
    3.5 Watts
  • Test Switch
    Single Pole
  • Battery
    High-Temperature, Maintenance-Free
    Nickel-Cadmium Battery
    7- to 10-Year Life Expectancy
  • Battery Charging Current
    280 mA
  • Recharge Time
    24 Hour
  • Charging Indicator Light
    LED
  • Temperature Rating (Ambient)
    0°C to +55°C (32°F to 131°F)
  • Dimensions
    9.4" x 2.4" x 1.5"
    (238 mm x 60 mm x 38 mm)
    Mounting Center 8.9" (226 mm)
  • Weight
    2.5 lbs. (1.13 kg) 
    Stock Code Bodine_B70A-CAN
    Brand Philips
    Family CSA Certified Emergency Lighting Equipment
    Part No B70A-CAN
    Length (in) 9.4" (238mm)
    Width (in) 2.4" (60mm)
    Height (in) 1.5" (38mm)
    Voltage (V) 120/347V, 60Hz
    Input Current 0.28A
    Wattage (w) 3.5 Watts
    Bulb Type Fluorescent Lamps
    Switch Type: Test Switch: Single Pole
    Lumens (Initial) 700 Lumens
    Battery Back Up Yes
    Battery Type: High-Temperature, Maintenance-Free Nickel-Cadmium Battery 7- to 10-Year Life Expectancy
    Recharge Time: 24 Hrs
    Max. Charge Current 280mA
    Operates one 17 - 32 W T8 or with one 20 - 40 W T10 or T12 fluorescent lamp.
    Start Temp. (Min) 0°C (32°F)
    Start Temp. (Max) 55°C (131°F)
    Weight (lb.) 2.5 lbs
    UL Listed UL, CSA and Code Compliance
    Case Quantity 1
    Warranty 3 Years (NOT pro-rata)
    Notes The B70A-CAN can be used with most 17 - 215 W (2’ - 8’) T8, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving, and (4-pin) compacts. It is also compatible with most one-, two-, three- or four-l
     